InteliLite4 AMF20 Global Guide
246
Sd overspeed option will result in controller shutting down the engine and displaying Sd Starting
Overspeed alarm and NextStartAt option will result in controller stopping the engine and trying to start
again. The number of attempts is defined by
Underspeed Sd
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 ..
[%]
Default value
25%
Alternative config
NO
Step
1 % of
Comm object
8260
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for underspeed protection. Relative to the nominal speed.
Oil Pressure Delay
Setpoint group
User Setpoints
Related FW
1.3.0
Range [units]
0.0 .. 3600.0 [s]
Default value
3.0 s
Alternative config
NO
Step
0.1 s
Comm object
65535
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
user protection.
Oil Pressure Wrn
Setpoint group
User Setpoints
Related FW
1.3.0
Range [units]
0.0 .. 10.0 [bar]
Default value
2.0 bar
Alternative config
NO
Step
0.1 bar
Comm object
65534
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for
user protection.