InteliLite4 AMF20 Global Guide
211
SplPhL1L2
L1 >=100 V
L2 >= 100 V
L3 <= 20 V
Mono Phase
L1 >=100 V
L2 <= 20 V
L3 <= 20 V
Voltage Autodetect shutdown
Nominal Voltage Ph-N
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
80 .. 20 000 [V]
Default value
231 V
Alternative config
YES
Step
1 V
Comm object
8277
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal voltage (phase to neutral).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Voltage Ph-N 2 (page 378)
and
Nominal Voltage Ph-N 3 (page 383)
.
Nominal Voltage Ph-Ph
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
80 .. 40 000 [V]
Default value
400 V
Alternative config
YES
Step
1 V
Comm object
11657
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal system voltage (phase to phase).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Voltage Ph-Ph 2 (page 378)
and