InteliLite4 AMF20 Global Guide
209
CT Location
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
Load / Gen-set / None [-]
Default value
Gen-set
Alternative config
NO
Step
[-]
Comm object
11625
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
This setpoint adjusts position of current measurement.
Load
Current CT's are physically placed on Load (typically between GCB and MCB).
Gen-set
Current CT's are physically placed on Gen-set (typically before GCB).
None
There are no current CT's.
When option None is selected, following objects are hidden/changed:
Current screen is hidden
Generator Power screen is hidden
Statistics screens – values Gen-set kWh, Gen-set kVArh, Mains kWh and Mains kWArh are hidden
Main screen – kW meter is replaced by generator voltage meter
Generator L1-N voltage is displayed for Monopahse, Splitphase L1L2, Splitphase L1L3 and
High Leg delta connection types
Generator L1-L2 voltage is displayed for 3ph3w and 3ph4w connection types
Group Load is hidden
Group Statistics – values Gen-set kWh, Gen-set kVArh, Mains kWh and Mains kWArh are hidden
Subgroup: Voltage settings
Connection type
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
Mono Phase / SplPhL1L2 / SplPhL1L3 / 3Ph3Wire / 3Ph4Wire / High Leg D /
Autodetect [-]
Default value
3Ph4Wire
Alternative config
YES
Step
[-]
Comm object
11628
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Connection type: