InteliLite4 AMF20 Global Guide
210
Mono Phase
Single phase voltage measurement L1-N
1x CT (Current Transformer)
SplPhL1L2
Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
SplPhL1L3
Double Delta connection
Split Phase
Two phase voltage measurement L1,L3 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire
Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
3Ph4Wire
Grounded Star (Grounded Wye) connection – 3PY
Three phase voltage measurement L1,L2,L3 with 120° phase shift
3x CT (Current Transformer)
High Leg D
High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
Autodetect
High Leg Delta
L1 >=100 V; L1 <=140 V
L2 >=140 V
L3 >=100 V; L3 <=140 V
3Ph Low Y
L1 <=160 V
L2 <=160 V
L3 <=160 V
3Ph High Y
L1 >160 V
L2 >160 V
L3 >160 V
SplPhL1L3
L1 >=100 V
L2 <= 20 V
L3 >=100 V