InteliLite4 AMF20 Global Guide
503
This output is dedicated to control the stop solenoid (valve). The output is activated when an engine stop
command is received and is deactivated 12 s after last running engine indication went off, i.e. engine is
stopped.
Image 8.59 Stop Solenoid 1
Image 8.60 Stop Solenoid 2
Note:
If
Additional running engine indications (page 114)
went off during 5 s pause than Stop
Solenoid is not activated again otherwise stop solenoid is activated again.