212
Nominal Voltage 3Ph Low Y
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
80 .. 20 000 [V]
Default value
120 V
Alternative config
YES
Step
1 V
Comm object
20811
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible if one of the three
Setpoints is set to
Autodetect.
Description
This setting is used as phase-neutral
Nominal Voltage Ph-N (page 211)
by the voltage autodetect
function, if detected
is 3Ph Low Y (controller can not distinguish between
the 4 wire and 3 wire connection), detected phase-phase voltage is lower than 300 V in all three phases
and phase-neutral voltage is lower than or equal to 160 V in all three phases.
Nominal Voltage 3Ph High Y
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
80 .. 20 000 [V]
Default value
277 V
Alternative config
YES
Step
1 V
Comm object
20812
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible if one of the three
Setpoints is set to
Autodetect.
Description
This setting is used as phase-neutral
Nominal Voltage Ph-N (page 211)
by the voltage autodetect
function, if detected
is 3Ph High Y, detected phase-phase voltage is higher
than or equal to 300 V in all three phases and phase-neutral voltage is higher than 160 V in all three
phases.