InteliLite4 AMF20 Global Guide
207
Nominal Power Split Phase
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
1 .. 5 000 [kW]
Default value
200 kW
Alternative config
YES
Step
1 kW
Comm object
9977
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal power of the Gen-set for detected split-phase or mono phase connection. Generator
protection is based on this setpoint.
Note:
This setpoint is used when setpoint
is adjusted to Autodetect and
Autodetect detects connection type as Monophase or Splitphase.
Note:
To lock this setpoint against editing you also have to lock setpoint
,
Nominal Power Split Phase 2 (page 382)
and
Nominal Power Split Phase 3 (page
Subgroup: Current settings
Nominal Current
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
1 .. 10 000 [A]
Default value
350 A
Alternative config
YES
Step
1 A
Comm object
8275
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
It is current limit for mains current protections and means maximal continuous mains current. Nominal
Current can be different from mains rated current value.
Note:
To lock this setpoint against editing you also have to lock setpoint
and