InteliLite4 AMF20 Global Guide
374
Nominal Current 1
Setpoint group
Alternate Config
Related FW
1.3.0
Range [units]
1 .. 10 000 [A]
Default value
350 A
Alternative config
YES
Step
1 A
Comm object
12049
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
It is current limit for generator current protections and means maximal continuous generator current.
Nominal Current can be different from generator rated current value.
Note:
This value is used when any other alternate configuration is not active.
Connection Type 1
Setpoint group
Alternate Config
Related FW
1.3.0
Range [units]
Mono Phase / SplPhL1L2 / SplPhL1L3 / 3Ph3Wire / 3Ph4Wire / High Leg D /
Autodetect [-]
Default value
3Ph4Wire
Alternative config
YES
Step
[-]
Comm object
12058
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Connection type:
Mono Phase
Single phase voltage measurement L1-N
1x CT (Current Transformer)
SplPhL1L2
Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
SplPhL1L3
Double Delta connection
Split Phase
Two phase voltage measurement L1,L3 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire
Ungrounded Delta connection
Open Delta
Ungrounded Wye