InteliLite4 AMF20 Global Guide
260
Maintenance Timer 3 Protection
Setpoint group
Maintenance Timers
Related FW
1.3.0
Range [units]
Warning / BOC [-]
Default value
Warning
Alternative config
NO
Step
[-]
Comm object
20588
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Type of the maintenance alarm of both
Maintenance Timer 3 RunHours (page 259)
and
.
Group: Generator settings
Subgroup: Overload Protection
Overload BOC
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
.. 200 [%]
Default value
120 %
Alternative config
NO
Step
1 % of
Comm object
8280
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold level for overload of generator (in % of Nominal power) protection. Protection is BOC (Breaker
Open and Gen-set Cooldown).
Note:
When there is no control of breakers, the type of protection is Sd not BOC.