InteliLite4 AMF20 Global Guide
206
Group: Basic settings
Subgroup: Name
Gen-Set Name
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
0 .. 15 characters [-]
Default value
InteliLite
Alternative config
NO
Step
[-]
Comm object
8637
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
User defined name, used for the controller identification at remote phone or mobile connection. Gen-set
Name is maximally 15 characters long and can be entered using InteliConfig or from controller's
configuration menu.
Note:
If the Gen-set Name is "TurboRunHours", the running hours will be counted faster – 1 minute in
real will represent 1 hour.
Subgroup: Power settings
1.3.0
YES
AMF, MRS
Nominal power of the Gen-set. Generator
protection is based on this setpoint.
Note:
This setpoint is used when setpoint
is adjusted to Monophase or
Splitphase or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect detects connection type as
3Ph3Wire or High Leg D or 3Ph4Wire.
Note:
To lock this setpoint against editing you also have to lock setpoint
and
.