InteliLite4 AMF20 Global Guide
386
ECU Speed Adjustment 3
Setpoint group
Alternate Config
Related FW
1.3.0
Range [units]
0 .. 100 [%]
Default value
50 %
Alternative config
NO
Step
1 %
Comm object
15199
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.
Note:
This value is used when binary input
is active.
Nominal Power 3
Setpoint group
Alternate Config
Related FW
1.3.0
Range [units]
1 .. 5 000 [kW]
Default value
200 kW
Alternative config
YES
Step
1 kW
Comm object
12048
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Nominal power of the Gen-set. Generator
protection is based on this setpoint.
Note:
This setpoint is used when setpoint
is adjusted to Monophase
or SplitphaseL1L2 or SplitphaseL1L3 or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect
detects connection type as 3Ph3Wire or High Leg D or 3Ph4Wire.
Note:
This value is used when binary input
is active.