InteliLite4 AMF20 Global Guide
143
Power is above level set by
– in this case controller will wait for time set by
setpoint
Dummy Load Off Delay (page 288)
before deactivating the highest active stage of Dummy
Load (If
are active, controller will
deactivate
). If no Dummy Load outputs are active, nothing will happen.
Controller will always work only with Dummy Load Stages up to highest one configured (if you only
configure
and
, there will effectively
only be two stages and if
is already active and
timer collapses,
will be activated but there will be no
timer for
.
IMPORTANT: Check how big your load bank is and set the
and
setpoints to correct levels, so that when dummy load is activated ,
power will not immediately go over the
5.5.18 Sensor curves
Background of the sensor calibration
To correct measuring error of each analog input (pressure, temperature, level, etc.), calibrating constants
should be set. To correct an offset of each analog input, select an option Offset in InteliConfig and set the
appropriate value.
Note:
The calibration must be done at the operational point of the analog input (e.g. 80 °C, 4.0 Bar etc..)
Default sensor curves
There are 16 default resistive curves available. The following table provides information on
minimum/maximum values of respective sensors. Actual values especially of temperature curves may differ.
The purpose is to prolong curve to the lower temperature values, so the cold engine will not raise alarm failure
sensor.