InteliLite4 AMF20 Global Guide
597
All 8 inputs are always configured to one type (HSS/LSS) together. All 8 outputs can be modified to inputs by
switch on the PCB ( Inteli IO8/8 to Inteli IO16/0).
Analog outputs
2 channels
can be configured as:
voltage 0-10V
current 0-20mA
PWM (level 5 V, with adjustable frequency from 200 Hz to 2400 Hz, with step 1 Hz)
All inputs/outputs can be configured to any logical function or protection.
Output state check
Output state check function evaluates in real time the state of binary outputs and adjusted (required) state. In
case of failure (a difference between the required state and real state) history record and alarm are issued
(type of the alarm is set by "Protection upon module failure" – (No protection / Warning / Shutdown)).
This function is designed for short-circuit or other failure, which causes change of set state of binary output.
CAN address
In Inteli IO8/8 mode CAN address for binary inputs is determined by DIP switch A, CAN address for binary
output and analog outputs is determined by DIP switch B.
In Inteli IO16/0 mode CAN address for binary inputs is determined by DIP switch A, first group of 8 input has
address A, second group of 8 inputs has address A+1. CAN address of analog outputs is set by DIP switch B.
Note:
When setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Remove the top cover of module
3. Put the TEST jumper on pins