InteliLite4 AMF20 Global Guide
261
Overload Wrn
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
0 ..
[%]
Default value
120 %
Alternative config
NO
Step
1 % of
Comm object
9685
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold level for overload of generator (in % of
) protection. This is only
warning.
Overload Delay
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
0.0 .. 600.0 [s]
Default value
5.0 s
Alternative config
NO
Step
0.1 s
Comm object
8281
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for protections
and
Subgroup: Current Protection
Short Circuit BOC
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
100 .. 500 [%]
Default value
250 %
Alternative config
NO
Step
1 % of
Comm object
8282
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Protection occurs when generator current reaches this preset threshold. Type of the protection is BOC.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.