InteliLite4 AMF20 Global Guide
604
CAN address
Controller type selection
The type of controller to be used with IGS-PTM must be selected via jumper labelled IGS accessible at the
lower PCB.
IGS jumper
Controller type
OPEN
IL-NT, IC-NT
CLOSE
IG-NT, IS-NT, InteliLite
Address configuration
If InteliLite controller type is selected (by IGS jumper), address of IGS-PTM could be modified via jumpers
labelled ADR1 and ADR2.
ADR1
ADR2
ADR offset
BIN module
BOUT
module
AIN module
Open
Open
0 (default)
1
1
1
Close
Open
1
2
2
2
Open
Close
2
3
3
3
Close
Close
3
4
4
4
Programming firmware
Firmware upgrade is available via AT-link (TTL). For programming it is necessary to close jumper BOOT.
RESET jumper is used to reset the device. Close jumper to reset the device. For programming FlashProg PC
tool should be used.
LED indication
Binary input
Each binary input has an LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has an LED which indicates output signal. Binary output LED is shining when binary
output is set.
LED at power connector – status LED
LED status
Description
Dark
No required power connected.
Quick flashing
Program check failure.
One flash and pause
Compensation fail.
Three flashes and
pause
Compensation successful.
Flashes
There is no communication between IGS-PTM and the controller.
Lights
Power supply is in the range and communication between IGS-PTM and
controller properly works.