InteliLite4 AMF20 Global Guide
504
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
1249
Description
The binary output depends on measured generator active power. Power is compared with generator
nominal active power with use of hysteresis and with delay of switch 1 s.
When the measured active power is equal to or bigger than 5 % of
for 1 s
then the binary output is active.
When the measured active power is equal to or lower than 3 % of
for 1 s then
the binary output is inactive.
Supplying Load
back to Logical binary outputs alphabetically
LBO: V
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
38
Description
This logical binary output is activated at the beginning of start procedure together with
LBO. Ventilation output is deactivated when engine stops revolving.
Ventilation LBO is also deactivated immediately when
(or E-Stop) is
activated or when controller is switched to OFF mode.
Note:
The output is intended for control of an engine room ventilation fan, engine container ventilation
fan, container louvres or similar running gen-set technology.
Ventilation
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
2090
Description
This logical binary output is activated on falling edge of
LBO (when engine stops).
The pulse duration is adjusted by
Ventilation Pulse Time (page 255)
setpoint.
Note:
The output is intended for control of an engine room ventilation fan, engine container ventilation
fan, container louvres or similar running gen-set technology.
Ventilation Off Pulse
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
2089
Description
This logical binary output is activated on rising edge of
LBO (at the begining of
prestart period). The pulse duration is adjusted by
Ventilation Pulse Time (page 255)
setpoint.
Ventilation On Pulse