InteliLite4 AMF20 Global Guide
255
Subgroup: Ventilation
Ventilation Pulse Time
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0–3600 [s]
Default value
30 s
Alternative config
NO
Step
1 s
Comm object
15767
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Only when logical binary output
or
is configured.
Description
This setpoint defines duration of pulse generated on logical binary outputs
or
at the moment when logical binary output
is activated or deactivated respectively.
Subgroup: ECU Settings
ECU Speed Adjustment
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 .. 100 [%]
Default value
50 %
Alternative config
NO
Step
1 %
Comm object
9948
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50 %. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.