InteliLite4 AMF20 Global Guide
414
Maintenance Timer 3 Interval
Value group
Statistics
Related FW
1.3.0
Units
days
Comm object
16389
Related applications
AMF, MRS
Description
Countdown until next maintenance 3.
Statistic value for
Maintenance Timer 3 Interval (page 259)
.
Num E-Stops
Value group
Statistics
Related FW
1.3.0
Units
[-]
Comm object
11195
Related applications
AMF, MRS
Description
Emergency stop alarms counter.
Note:
This value counts only in case that Gen-set was stopped due to E-Stop or Emergency Stop.
Shutdowns
Value group
Statistics
Related FW
1.3.0
Units
[-]
Comm object
11196
Related applications
AMF, MRS
Description
Shutdown alarms counter. This counter counts all occurrences of a shutdown alarm, not only real
shutdowns of the Gen-set, i.e. the counter is increased by 2 if two shutdown alarms appear
simultaneously.
Total Fuel Consumption
Value group
Statistics
Related FW
1.3.0
Units
L
Comm object
9040
Related applications
AMF, MRS
Description
Value containing total amount of consumed fuel by engine. The controller automatically updates this value
every 30 s. The controller can calculate it in three ways:
Direct reading from ECU
Calculation based on actual fuel consumption reading from ECU
Calculation from fuel level drop in tank (using Fuel Level Analog Input)