InteliLite4 AMF20 Global Guide
487
LBO: I
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
39
Description
This output is used for switching between idle speed and nominal speed of the engine during the startup
phase, if this feature (input) is available on the particular engine. In the case of some EFI engines, the
idle/nominal switching is performed over the communication bus.
The output Idle/Nominal is activated after the timer
elapses. The
starts to countdown when
reached. The underspeed protection is not
evaluated during fixed 5 seconds period after reaching
. A Start Fail protection
occurs if the RPM drop below 2RPM during idle.
Image 8.44 Idle/Nominal
Note:
Connect binary output Idle/Nominal to speed governor to switch the speed:
opened = Idle
closed = Nominal
(for normally open contact type)
Idle/Nominal
back to Logical binary outputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
37
Description
This output is dedicated to controlling the ignition at a gas engine. the output is active together with binary
output
in the moment when the Gen-set reaches at least 30 RPM during
cranking. The output is deactivated 500 ms after all
Additional running engine indications (page 114)
will be inactive. the output is deactivated when the Gen-set has to be stopped or in pause during repeated
starts.
Ignition