InteliLite4 AMF20 Global Guide
235
Subgroup: Starting Timers
Fuel Solenoid Lead
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0,0 .. 25,0 [s]
Default value
0,5 s
Alternative config
NO
Step
0,1 s
Comm object
10525
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Delay between
and
logical binary outputs.
is active before
. Lead time is adjusted via this setpoint.
Image 8.2 Fuel Solenoid Lead
Note:
LBO
goes to logical zero when Fuel Solenoid Lead goes to logical one.
Note:
This setpoint is used only for diesel
Idle Time
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 .. 600 [s]
Default value
12 s
Alternative config
NO
Step
1 s
Comm object
9097
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Idle Time delay starts when RPM exceeds
. Start fail is detected when during
Idle state RPM decreases below 2 RPM.
The output
remains inactive during the idle period. Binary output Idle/Nominal