InteliLite4 AMF20 Global Guide
161
Point 11 – Configuration download
Current archive is download to USB flash drive (Name = SN_YYMMDDHHMM).
Confirmation pop-up message: "Archive successfully saved"
5.5.24 Firewall
The firewall function allows to restrict the access to the controller application services (ComAp/TCP server,
MODBUS/TCP server etc.) or to the specific computers or networks. Firewall can be activated on Ethernet port.
Example:
Adress:
192.168.1.0
Netmask:
255.255.255.0
Port:
23
Any computer with IP address from the network range 192.168.1.0 – 192.168.1.255 can connect to
ComAp/TCP server (= connect to the controller with InteliConfig via Ethernet).
Example:
Adress:
192.168.1.100
Netmask:
255.255.255.255
Port:
502
Only the single computer with IP address 192.168.1.100 can connect to MODBUS/TCP server
IMPORTANT: When enabling the firewall, If the rules are not set up properly and the connection is
made remotely, loss of connection can happen.
5.5.25 E-Stop
Binary outputs for the control of some essential functions are internally wired as "safe", meaning that their
deactivation is directly bound with the dedicated Input E-STOP (not evaluated as the LBI in the controller).
These BO are fully configurable and are used e.g. for the Starter and Fuel control.
The emergency stop circuit must be secured.
The power supply of the associated binary outputs (BOUT1 and BOUT2) is supplied by the E-STOP input,
not by the + battery voltage.
Note:
There is no difference in the way of configuration of all binary outputs. Binary outputs BO1 (Starter),
BO2 (Fuel Solenoid) are intended for these functions (not dedicated).
There is a measurement of E-STOP input voltage analogically and setting the binary value (representing
emergency stop input level) based on comparison of the measured voltage to two analog levels, which are
derived from the controller supply voltage (battery voltage) perceptually.