InteliLite4 AMF20 Global Guide
267
Subgroup: Frequency Protection
Generator Overfrequency BOC
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
Generator Overfrequency Wrn (page 267)
.. 200,0 [%]
Default value
110,0 %
Alternative config
NO
Step
0,1 % of
Comm object
8296
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator phase L1 overfrequency.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Generator Overfrequency Wrn
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
Generator Underfrequency Wrn (page 267)
..
[%]
Default value
110,0 %
Alternative config
NO
Step
0,1 % of
Comm object
9688
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator phase L1 overfrequency.
Generator Underfrequency Wrn
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
Generator Underfrequency BOC (page 268)
..
[%]
Default value
85,0 %
Alternative config
NO
Step
0,1 % of
Comm object
9689
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator phase L1 underfrequency.