InteliLite4 AMF20 Global Guide
266
Generator <> Voltage Delay
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
0,0 .. 600,0 [s]
Default value
3,0 s
Alternative config
NO
Step
0,1 s
Comm object
9103
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
Generator Overvoltage Sd (page 264)
Generator Overvoltage Wrn (page 264)
and
Generator Undervoltage Wrn (page 265)
protection.
Voltage Unbalance BOC
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
1 .. 200 [%] of
Nominal Voltage Ph-Ph (page 211)
or
Default value
10 %
Alternative config
NO
Step
1 %
Comm object
8288
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Threshold for generator voltage unbalance alarm.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Voltage Unbalance BOC Delay
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
0.0 .. 600.0 [s]
Default value
3.0 s
Alternative config
NO
Step
0.1 s
Comm object
8289
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Delay for
Voltage Unbalance BOC (page 266)
protection.