InteliLite4 AMF20 Global Guide
270
MCB Close Delay
Setpoint group
Mains Settings
Related FW
1.3.0
Range [units]
0.0 .. 600.0 [s]
Default value
1.0 s
Alternative config
NO
Step
0.1 s
Comm object
8389
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
Delay after mains returns to MCB closing, if the Gen-set is not running (e.g. is in start-up procedure).
Transfer Delay
Setpoint group
Mains Settings
Related FW
1.3.0
Range [units]
0.0 .. 600.0 [s]
Default value
1.0 s
Alternative config
NO
Step
0.1 s
Comm object
8303
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
Transition Delay between power sources.
Delay after GCB opening to MCB closing during the return procedure. Delay after MCB opening to GCB
closing if the setpoint
is set to GENRUN.
The time charts bellow show recommended setting of Transfer Delay setpoint.
If the Transfer Delay setpoint is set shorter than the time required for opening of the circuit breaker, the
controller closes
output straight away (100 ms) after the
input deactivates.