InteliLite4 AMF20 Global Guide
263
Image 8.15 IDMT Overcurrent Delay
Current Unbalance BOC
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
1 .. 200 [%] of
Default value
50 %
Alternative config
NO
Step
1 % of
Comm object
8284
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Threshold for generator current asymmetry (unbalance).
Protection is BOC (Breaker Open and Gen-set Cooldown).
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Current Unbalance BOC Delay
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
0.0 .. 600.0 [s]
Default value
5.0 s
Alternative config
NO
Step
0.1 s
Comm object
8285
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Delay for
Current Unbalance BOC (page 263)
protection.