1BPROTECTION FUNCTIONS
PROTECTION, CONTROL AND METERING FUNCTIONS
"Bus Voltage supervision”, shown in Table 2-25
Setting
Minimum
Maximum
Step
Notes
Enable
SI/NO
Reference
Voltage(V)
0
10,5
0,01
Para Vn = 6,5V
0
3000
0,01
Para Vn =
115V
Check time (s)
0
60
0,01
Table 2-25 Setting range for the bus voltage supervision during the reclose cycles
2.1.16. COLD LOAD PICKUP
2.1.16.1. DESCRIPTION
This function aims to avoid non wanted trips when the line is energized after being
de-energized for a period of time; in this situation the load can exceed the protection
setting without the presence of a fault. The function detects those conditions and
changes the trip settings for a programmable time.
The function is activated when the current in the 3 phases is below 10% of the
nominal relay current for a time greater than the “Cold load time” configurable
parameter indicates. This is interpreted by the smART P500 as a load loss situation.
Once activated, the protection’s usual settings are replaced by the cold load pick-up
settings. These cold load pick-up settings will remain active until at least one of the
measured currents rises above 20% of the nominal relay current, remaining there for
the configured “Pick-up time”, time after which the function is deactivated and the
cold load pick-up settings are replaced by the usual settings. So, there are two
configurable times for this function, named “Cold load time” and “Pick-up time”,
besides the desired IOC and TOC settings to be in effect during the cold load pick-up
period.
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...