5BMETERING FUNCTIONS
PROTECTION, CONTROL AND METERING FUNCTIONS
2.5.1. DEMAND INTEGRATION
The demand is the average value in a defined interval named Demand integration
interval (DII), with units related to the electrical parameter measured (kW, kVAR, kVA,
etc.)
The demands of the following proART relay parameters can be calculated (see Table
2-31):
Parameter
Description
Parameter
Description
Ia
Phase a current
Qa
Phase a reactive power
Ib
Phase b current
Qb
Phase b reactive power
Ic
Phase c current
Qc
Phase c reactive power
In (3Io)
Neutral current
Sa
Phase a aparent current
Ig
Ground current
Sb
Phase b aparent current
Va
Phase a voltage
Sc
Phase c aparent current
Vb
Phase b voltage
P3
3 phase active current
Vc
Phase c voltage
Q3
3 phase reactive current
Pa
Phase a active power
S3
3 phase aparent current
Pb
Phase b active power
3I
1
Positive sequence current
Pc
Phase c active power
3I
2
Negative sequence current
Table 2-31 Parameters of demands calculated
The calculation method can be programmed as block or thermal demands.
2.5.1.1. BLOCK DEMAND INTEGRATION
To calculate the block demand the relay uses two user defined parameters;
Intervals to be integrated (IBI):
is the number of intervals to be considered to
calculate the demand. It could be between 1 and 15. For direct integration (non
rolling) a 1 must be programmed. For rolling demand a value between 2 and
15 must be programmed, normally 3 is used for rolling demand
Integrate every (IE):
Is the period of time between two demand integrations
and can be selected from 1 second to 60 minutes. Normal values are 15
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...