2BOTHER FUNCTIONS
PROTECTION, CONTROL AND METERING FUNCTIONS
Figure 2-49 Breaker Monitor Function
2.2.2.2. SETTING RANGEs (1 GROUP)
The settings for this function are the following in Table 2-27
Setting
Minimum
Maximum
Step
Notes
Enable
YES/NO
Excessive nº. of trips
1
254
1
N trips time window (s)
300
3,600
1
Σ
kI
2
alarm theresold
0
65,535
1
Calculation type
kI, kI
2
, kI
2
T
Table 2-27 Setting ranges of breaker monitor
2.2.3. MELTING FUSE
If enabled, after the programmed closure cycle (1 to 3), the protection changes
automatically the protection group it is working with, enabling then a group previously
programmed by the user. This settings change enables the increase of the protection
functions operation times and allows the protection fuses of the installation blow up
before the breaker acts. When the ongoing cycle is finished the original group is
activated again.
Num.
Programmed trips
blk74TC
blkAnyProt
r74 = 1
+
-
rAnyOCTrip
Num. trips
+
-
Elapsed Time
Programmed Time
Window
Interrupted Current
Accumulators
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...