8BCONTROL FUNCTIONS
PROTECTION, CONTROL AND METERING FUNCTIONS
Figure 2-70 SMS Telecontrol
Enable
: yes/no.
Authorized telephones list:
list of up to 5 telephones that can receive the
output messages and if the SMS command check box is activated can also
send SMS COMMANDS.
Validity:
Time in seconds for a command to be valid. Is the difference between
the server’s timestamp and the relays time when the command is received. Is
a number between 1 and 3600 seconds. If a 0 is established the command is
not evaluated.
Once the desired parameters have been set send them to the relay.
2.8.3.5. OUTPUT MESSAGES
Each output message will be formed by:
Relay name.
Relay location.
Message body, as in the Table 2-34:
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...