Installation Instructions

1. 

Device should be installed on DIN rail.

2. 

Device must be installed in an enclosure suitable for 

the application and environment for which it is being 

used. Connected Load shall not exceed 60 amps.

3. 

Confirm power is off prior to performing the 

installation.

4. 

Use the appropriate wire size and type based on the 

connected load and torque to the specified ratings.

5. 

Connect input and output connections and replace 

finger guard covers and restore power.

6. 

Confirm power LED is illuminated and proceed to 

programming functions.

To Enter Programming Mode

Push “Mode” button one time. There may be a delay up 

to one minute while the program finishes the active cycle. 

Setup will begin by displaying setting “A 0000”. Each time 

the mode button is pressed, the device advances to the 

next menu setting. Adjustments to the settings are made 

using the UP & DOWN buttons. The mode and settings 

are displayed on the LCD screen. The program mode 

exits and saves settings after 7 seconds of inactivity.

Set Mode “A” to 0000 to disable dry contact

control of relay.

Set Mode “b” to 0000 to enable load lockout

mode on Generator.

Set Mode “d” to a minimum of 000.2 to 

provide 12 second delay after power up.

Warning! Do not apply external voltage to the 

dry contact input terminals. This will damage 

the SAK-60 and void the warranty. 

L1-IN 

L2-IN

L1-OUT

L2-OUT

Dry Contact

Input

LCD Display

DOWN Button

UP Button

MODE  Button

Auxiliary Terminals

Main Terminals

LI OUT

LI IN

L2 OUT

L2 IN

U  240

SAK-60

Gen-Util LED

MODE

UP

DOWN

GEN-UTIL Load On

Load On LED

Main Terminals

CU7 Copper Conductors Only

10-14 AWG 35 IN. LBS.

8 AWG 40 IN. LBS.,

4-6 AWG 45 IN. LBS.

2-3 AWG 50 IN. LBS.

Auxiliary Terminals

CU7 Copper Conductors Only 12-16 AWG 20 IN. LBS.

 

Set To: 

Mode 

Adjustment Range 

Adjustment Details

Quick Start Chart : Load Lock-Out on Generator Settings

Quick Start Charts are provided to assist in setting up basic functions. The complete menu is available on 

the last pages of this document to assist with advanced functions and provide a better understanding of the 

program flow.

A

0000

0000

0000

A 0000

To

A 0003

 

000.1

To

 

999.9

SAK-60

Installation Programming Guide

Summary of Contents for SAK-60

Page 1: ...re displayed on the LCD screen The program mode exits and saves settings after 7 seconds of inactivity Set Mode A to 0000 to disable dry contact control of relay Set Mode b to 0000 to enable load lock...

Page 2: ...after generator is detected For multiple loads stagger restore times based on priority of loads connected Set Mode C to 0001 to enable pre set under frequency cut off points or set to 0000 to enable u...

Page 3: ...estoration this extended delay U is activated and added to setting O normal restore delay Time Delay 2 Set delay time from 00 1 to 10 0 seconds for under frequency 2 under frequency load shed Default...

Page 4: ...event short cycling of connected load Set Mode J to adjust the set point for over voltage cut off from 201 to 300 VAC Set mode L to adjust the delay before the load is restored after an over or under...

Page 5: ...management under frequency drop of loads when generator detected Active in mode b0001 only Adjust the delay time in minutes before restoring load after generator sine wave has been detected C 0000 to...

Page 6: ...00Hz follows delay d2 Under frequency mode C 0001 fixed 56 00 Hz Active when Menu C 0000 Under Frequency F3 Set from 50 00 to 60 00 Hz Default setting 52 00Hz follows delay d3 Under frequency mode C 0...

Page 7: ...VC III Pollution degree PD2 Rated Impulse Voltage 2500 V Maximum phase to ground voltage of the supply source 150 V Protection against electric shock class Insulation encased Class II Equipment Enviro...

Page 8: ...quency load management The first Mode C 0001 is fixed and the pre set under frequency and delay times cannot be adjusted These values should be suitable for most air cooled applications The second Mod...

Reviews: