1BPROTECTION FUNCTIONS
PROTECTION, CONTROL AND METERING FUNCTIONS
2.1.1.2.1. SETTING RANGES (6 GROUPS)
The settings for this function are independently set for the phases. Table 2-2
Settings range for the phase time
Settings
Minimum
Maximum
Step
Observations
Enable
YES/NO
Pickup(A)
0,02
20
0,001
For In =1 A
0,1
100
0,001
For In = 5 A
Time Multiplier (dial)
0,05
1,09
0,01
For IEC curves
0,5
30
0,01
For ANSI curves
0,5
15
0,01
For US curves
Time Adder
0
100
0,01
Minimun Response Time
Adder
0.013
1
0.001
Definite Time(s)
0
600
0,01
Table 2-2 Settings range for the phase time overcurrent elements
The electromechanical reset option is available which simulates the disc used in
electromechanical protections. For definite time the protection sends the trip signal
t seconds, after the activation of the pickup, t being the Definite Time setting.
Using curves, the time for the trip signal to be sent depends on the selected curve
(family and modifiers) and on the fault current. Protection functions are evaluated
every quarter of a cycle at the fundamental frequency and a half cycle acting time
can be achieved depending on the magnitude of the fault current.
Appendix I shows the equations for the time calculation as a function of the fault
current and the pickup current.
2.1.1.3. INSTANTANEOUS OVERCURRENT ELEMENTS (50P)
Two instantaneous elements are available (low level and high level) with an
additional time option Figure 2-2 shows the logical diagram of the instantaneous
phase overcurrent low level function.
Two instantaneous elements (low and high level)
Additional time
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...