6BTESTS AND STANDARS
INTRODUCTION
Fast transient bursts immunity tests.
IEC 61000-4-4 (2004) for ±4 kV levels at
the auxiliary and ground mains, voltage and current input and digital inputs and
outputs.
Radiofrecuency induced signals immunity tests.
IEC 61000-4-6 (1996) + A1
(2000), for 10 Vrms at the frequency range of 0,15 to 80 MHz (level 3) at the
auxiliary and ground mains voltage and current inputs and digital inputs and
outputs.
Surge immunity tests.
IEC 61000-4-5 (1995) + A1 (2000) for ±4 kV levels in
common mode and ±2 kV in differential mode, applied between the auxiliary
mains and grounds, voltage and current inputs and digital inputs and outputs.
Outages, sags and variations at the DC source immunity test
. IEC 61000-4-
29 (2000), outages of up to 50 ms for an auxiliary voltage of 48 Vdc y de 10 ms
for an auxiliary voltage of 24 Vdc, 60% and 1s sags for an auxiliary voltage of 48
Vdc and 10 ms for an auxiliary voltage of 24 Vdc, 30% and 1s sags both for 24
Vdc and 48 Vdc and voltage variations between 80% and 120% both for 24 and
48 Vdc.
DC source ripple immunity test
. IEC 61000-4-17 (2002), for peak to peak
ripple values of 10% of the auxiliary voltage both for 24 Vdc and 48 Vdc. The
ripple frequencies were 60 and 120 Hz in every case.
60 Hz magnetic field immunity tests.
IEC 61000-4-8 (2001), with continuous
levels of 100 A/m and pulses of 2 s/1000 A/m, for 60Hz.
Damped oscillatory magnetic field immunity test.
IEC 61000-4-10 (2001),
with 100 A/m levels.
Damped oscillatory waves immunity test.
IEC 61000-4-12 (1995)., damped
oscillatory waves of 100 kHz and 1 MHz with common mode applications of 2.5
kV and differential mode of 1 kV at the auxiliary and ground mains, voltage and
current inputs and digital inputs and outputs..
1 MHz damped waves immunity test.
IEC 60255-22-1 (2005), common mode
2.5 kV and 1 kV differential for auxiliary mains, voltage and current inputs and
digital inputs and outputs.
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...