background image

BE1-32R, BE1-32R O/U

1

APPLICATION

Pages 2 - 4

SPECIFICATIONS

Pages 4 - 8

EXTERNAL

CONNECTIONS

Pages 9 - 10

ORDERING

INFORMATION

Pages 11 - 12

The BE1-32R Directional Overpower Relay and the BE1-32 O/U Directional

Over/Underpower Relay are solid-state devices which provide versatility

and control in protecting machines against reverse power flow,

underpower and overpower conditions.

ADVANTAGES

• Measures Real Power - El cos 

Θ

.

• Wide variety of input configurations are available including single-phase

and three phase, 3 and 4 wire systems.

• Sensing ranges available from 0.5 to 6000 watts secondary.

• Instantaneous, definite and inverse timing characteristics available.

• Low input sensing and supply burdens.

• Qualified to the requirements of

-ANSI/IEEE C37.90.1-1989 and IEC 255 for fast transient and

  surge withstand capability;

-IEC 255-5 for impulse.

• UL Recognized under Standard 508, UL File #E97033.

ADDITIONAL INFORMATION

INSTRUCTION MANUAL

Request Publication 9-1711-00-990

UBU-5

3-96

P. O. BOX 269 HIGHLAND, ILLINOIS  62249, U.S.A.   PHONE 618-654-2341   FAX 618-654-2351

BE1-32R, BE1-32 O/U

DIRECTIONAL

POWER RELAY

Summary of Contents for BE1-32

Page 1: ...rations are available including single phase and three phase 3 and 4 wire systems Sensing ranges available from 0 5 to 6000 watts secondary Instantaneous definite and inverse timing characteristics av...

Page 2: ...and continues to run as a synchronous motor drawing sufficient power from the system to drive the prime mover Sustained motoring can cause severe damage to the prime mover The Directional Power Relay...

Page 3: ...rovide adequate protection for the distribution system the overpower function is used to sense overload conditions on each transformer and the underpower function is used to sense power flowing throug...

Page 4: ...nts If sensing input range 1 4 or 7 is selected the input transformers are capable of 7 A continuous current 10 A for 1 minute and 140 A for 1 second However reactive power is defined by the equation...

Page 5: ...sing type and their calibration Type A Sensing Single Phase Figure 7 The type A sensing configuration monitors line to neutral voltage and a single phase current of a three phase four wire circuit and...

Page 6: ...en 0 9 and 0 5 The range of voltage for proper operation is 40 to 150 percent of the nominal value When the calculated value for power exceeds the over power pickup setting or falls below the underpow...

Page 7: ...nverse time delayed trip is available for the overpower function only The inverse time delay curve is adjust able from 01 to 99 by means of a front panel thumbwheel switch Incrementing the thumbwheel...

Page 8: ...alified to ANSI IEEE C37 90 1 1989 Fast Transient Test IMPULSE TEST Qualified to IEC 255 5 MECHANICAL Operating Temperature 40 C 40 F to 70 C 158 F Storage Temperature 65 C 85 F to 100 C 212 F Weight...

Page 9: ...BE1 32R BE1 32R O U 9 CONNECTIONS Figure 13 Sensing Connections Continued overpage 52 BE1 32 A B C N 5 6 8 9 TYPE A SENSING GENERATOR TRIPPING DIRECTION...

Page 10: ...10 BE1 32R BE1 32R O U CONNECTIONS continued Figure 14 Control Circuits Figure 13 continued Sensing Connections...

Page 11: ...he Style Number Identification Chart and entering its designation letter or number into the appropriate square Two squares are used to indicate time delay characteristics All squares must be completed...

Page 12: ...BER IDENTIFICATION CHART ROUTE 143 BOX 269 HIGHLAND ILLINOIS U S A 62249 PHONE 618 654 2341 FAX 618 654 2351 P A E Les Pins 67319 Wasselonne Cedex FRANCE PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http...

Reviews: