5BTIMES
0BMODBUS RTU PROTOCOL
5.5. TIMES
Package synchronization on the MODBUS protocol is maintained using time restrictions.
When a device receives a message it calculates the time elapsed between the receptions
of two consecutive characters. If the transmission time equivalent to 3.5 characters is
elapsed without receiving any further information, the device considers that the newly
received information is complete and checks the CRC, accepting or rejecting the message
depends on the result of the CRC check.
5.6. FUNCTIONS IMPLEMENTED IN THE SMART P500
The smART P500 relay is capable of responding to the following function codes:
03: Read input registers
04: Read holding registers
05: Force single coil
07: Read exception status
08: Diagnostics
16: Preset multiple registers
5.6.1. FUNCTION CODES 03 AND 04 – READING OF VALUES
In the smART P500 implementation, the function codes 3 and 4 are interchangeable.
Both can be used to read values from the relay.
Each value has an address and its length is 16 bits (2 bytes). The most significant byte
is transmitted first. Up to 125 adjacent values can be read in one operation.
However, the expression of some values of the relay has a length of 32 bits. To obtain
such values, 2 points must be read in the same operation. If it is not so the result may
be incorrect. The 16 most significant bits (MSB) are read first (have a lower address).
The 16 least significant bits (LSB) are read last (in the higher address).
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...