4BRELAY SETTINGS
0BDEVICE CONFIGURATION
Figure 3-52 Intermediate reclose settings
3.4.3. CAPACITOR BANK CONTROL
The smART P500 BC protective relay has the following operation modes:
Reactive Flow: Switching of Capacitor Bank depends on the values of reactive
power
Clock: Switching of Capacitor Bank depends on the level of measured voltage
and the programmed time schedule
3.4.3.1. REACTIVE FLOW CONTROL
Figure 3-53 shows the configuration window for this type of control.
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...