1BPROTECTION FUNCTIONS
PROTECTION, CONTROL AND METERING FUNCTIONS
2.1.16.2. SETTINGS (6 GROUPS)
Just as for the rest of the protection functions a set of setting tables exist for this
function:
Phase instantaneous/definite time/inverse time.
Neutral instantaneous/definite time/inverse time.
Sensitive instantaneous/definite time/inverse time.
Grouped into “Cold load pickup” there are the settings that define the operation of the
function:
“Cold load” function enable: YES/NO
“Cold load” time: 0 to 10000 second
“Cold load” duration (Pickup) time: 0 to 3600 seconds (1 hour)
During this time, all the overcurrent protection settings (phase, neutral and
sensitive neutral) stop corresponding to the “active table” and start
corresponding to the “cold load” settings: enabling actions, pickups, curves,
times etc
Remarks:
The “Cold load” function can be disabled with a digital input
The function “cold load” is de-activated while the unit is on “ongoing cycle”, this
means while the closing control is assumed by the Reclosing function
The function “cold load” does not operate on the “High Current Lockup”
settings.
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...