![background image](http://html1.mh-extra.com/html/arteche/smart-p500/smart-p500_instruction-manual_2977391357.webp)
POINT LIST
0BDNP3 PROTOCOL PROFILE
Variable
Description
Scale
Units
VA
Total Apparent Power (Three-Phase System)
1
VA
FP
Total Power Factor (Three-Phase System)
0,001
---
Temp
Temperature
0,5
°C
Load Side
Vs
Magnitude for Voltage CA
0,001
V
AngVs
Angle for Voltage CA
0,001
Grades
Frec2
Frequency
0,01
Hz
4.5.2. COUNTERS
A list of the counters that can be configured using proART® software is presented in the
following table. Column “Scale” is interpreted as an equivalence in engineering units.
Counters
Description
Scale
Units
Wh3P
Energy Accumulator Named Wh3+
1
kWh
Wh3N
Energy Accumulator Named Wh3-
1
kWh
VArh3I
Energy Accumulator named VArh3I
1
kVArh
VArh3II
Energy Accumulator named VArh3II
1
kVArh
VArh3III
Energy Accumulator named VArh3III
1
kVArh
VArh3IV
Energy Accumulator named VArh3IV
1
kVArh
VAh3
Energy Accumulator named VAh3
1
kVArh
KI_A
Accumulator of kI, kI2 or kI2t of the phase A
0,001
kA, (kA)
2
,
(kA)
2
s
KI_B
Accumulator of kI, kI2 or kI2t of the phase B
0,001
kA, (kA)
2
,
(kA)
2
s
KI_C
Accumulator of kI, kI2 or kI2t of the phase C
0,001
kA, (kA)
2
,
(kA)
2
s
CntOpen
Trip Counter (Openings)
1
Operation
CntRec1
Counter for 1st Reclose
1
Operation
CntRec2
Counter for 2nd Reclose
1
Operation
CntRec3
Counter for 3rd Reclose
1
Operation
CntRec4
Counter for 4th Reclose
1
Operation
CntRecT
Counter for Total Recloses
1
Operation
CntTrip50AA
Counter for High Phase A Trip
1
Operation
CntTrip50AB
Counter for High Phase B Trip
1
Operation
CntTrip50AC
Counter for High Phase C Trip
1
Operation
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...