2BGLOBAL SETTINGS
0BDEVICE CONFIGURATION
Location:
Identifier of the relay’s location.
Feeder Side:
Phase CT ratio:
Nominal turns-ratio of the instrument current transformer. This
ratio affects the current values reflected by the secondary at the relay and the
trip settings of the current protection functions.
Ground CT ratio:
Idem to the previous parameter but referenced to the neutral
current.
Phase PT ratio:
Nominal ratio of the instrument voltage transformer where the
relay is connected in feeder side. This ratio affects directly the voltage values
reflected by the secondary in the relay and the trip settings of several
protection functions.
Load Side:
Phase PT ratio:
Nominal ratio of the instrument voltage transformer where the
relay is connected in load side. This ratio affects directly the voltage values
reflected by the secondary in the relay and the trip settings of several
protection functions.
Voltage Wiring:
Can be selected between wye (4 wires), open delta (3 wires) or
phantom.
Default Active Settings Group:
Active settings group currently in use at the
relay. Six groups of different settings for the main protection functions can be
selected in this control. Each group has its own settings.
Phase Rotation:
Sequence of the analog input voltage. (ABC or ACB)
Frequency:
Frequency power system (60/50 Hz)
Summary of Contents for smART P500
Page 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Page 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Page 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Page 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Page 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Page 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Page 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Page 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Page 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Page 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Page 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Page 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...