background image

 

 

GE Energy Connections 

Grid Solutions 

MiCOM P40 Agile 

P14D, P14N, P94V 

Version History 

Feeder Management IED 
Hardware version: A 

Software version: Up to 61 

Publication reference: P40Agile-VH-EN-9 

Summary of Contents for MiCOM P40 Agile P14D

Page 1: ...GE Energy Connections Grid Solutions MiCOM P40 Agile P14D P14N P94V Version History Feeder Management IED Hardware version A Software version Up to 61 Publication reference P40Agile VH EN 9 ...

Page 2: ......

Page 3: ...ion CB Fail trip may fail to operate under faults with DC transient offsets IEC 61850 Client disassociation while reading PloGGIO1 CO block in P14D IEDs IEC61850 Measurements negative values rounding error Agile latch reset when setting group is changed What to do with Pending Reports when BufTm 0 Ed1 Undervoltage programmable curve not using standard template used by other Px4x relays The VCO Sta...

Page 4: ...er threads for up to 10ms Unextracted events are lost on RP1 following relay reboot using a DNPOE build Incorrect response to Object 2 Variation 3 request for Binary Input Event with Relative Time ISEF IEF and anything related are not scaled properly when the CT ratio is 5A IEEE Floats are wrong at modbus interface Ethernet application IEC61850 DNP3oe crashes if a Courier tunnel is continuously op...

Page 5: ...elay is set to primary in S1 53 D A Aug 2015 Very sharp pick current level lead relay tripping on IREF 53 E A April 2017 IEC 61850 Connection Disconnection issues DNP3oE Versions Courier Tunnelling doesnot work DNPOE after operated some DI and AI events at the same time the relay Ethernet board seems locked and after a while the relay reboot DNP Over Ethernet Application Crash after many days of P...

Page 6: ...urst Count HiF Detection FA Steady Fault Incorrect Assertion HIF CHA Hysteresis is not correctly set HIF Burst Threshold is not reset after the adaptive threshold is disabled Maintenance Record Generated Everytime Gateway is configured in DNP configuration 55 A A November 15 CS1 and CS2 does not work independently whey CB Comp enabled for CS2 To retrofit legacy products KAVR100 KAVS and KVTR Pin t...

Page 7: ...Fault Record after relay reboot P145 Underfrequency issue in Russia SecRmsMMXU1 showing values in primary not secondary IEC 61850 incorrect Courier cell mapping to TotWh and TotVArh in MMTR LNs CB Fail trip may fail to operate under faults with DC transient offsets FUNCTION KEYS column is visible for 20TE devices in P14 Agile data model Default GOOSE Min Cycle Time is wrong Visibility of setting I...

Page 8: ...ok Feel Start Elements Trip Elements available options Fault Record spread sheet need update Data Group Modbus missing Modbus Number of steps shift from cell 420D V 3 Function to 4211 V 3 Poledead Inh in Look Feel Max value 10Hz could not be set to cells f Df Dt x Dfreq x 1 to 9 via Modbus protocol The mapping Measurements SecMSTA1 MX AvVAr3 mag f was wrong it should map to the cell 0342 3Ph VAr F...

Page 9: ...P redundancy new hardware boards PCCN Electre features CEI 0 16 2nd round DNP3 memory leak correction AGPL 49 P14D TM EN 7 P14N TM EN 7 P94V TM EN 7 The values of DDBs 1717 1720 read via IEC61850 can not be updated after downloading the new PSL The fault record can t be extracted via CS103 protocol if the previous fault record terminated by Reset CU DNP Over Ethernet Application Crash after many d...

Page 10: ... events are read as test mode via CS103 protocol No events read from CS103 protocol for DDB 441 Test Mode DDB 771 GOOSE IED Absent DDB 780 IP Addr Conflict DDB 1200 Monitor bit 1 to DDB 1207 Monitor bit 8 IED reboot during the Endurance Test Stress Test at 69Hz Agile RSTP is non responsive at 10Mbps Relay contact 1 doesn t persist data on P14DH model after reboot 61 A A April 2017 TEFD new algorit...

Page 11: ......

Page 12: ...s document is indicative only No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project This will depend on the technical and commercial circumstances It is provided without liability and is subject to change without notice Reproduction use or disclosure to third parties without express written authority is strictly prohibi...