background image

Motorschutzrelais 
ZB12 und ZB32

Überlastüberwachung 
von EEx e-Motoren

Motor-protective 
relays ZB12 and ZB32

Overload monitoring of 
EEx e motors

Moeller GmbH
Industrieautomation
Hein-Moeller-Straße 7–11
D-53115 Bonn

E-Mail: [email protected]
Internet: www.moeller.net

© 2002 by Moeller GmbH
Subjekt to alteration
AWB2300-1527D/GB Doku/Doku/Eb 05/05
Printed in the Federal Republic of Germany (0x/05)
Article No.: 284910

4 *patpks#,v.y-,* 

cken

tex

t

Hardware und Projektierung
Hardware and Engineering

05/05 AWB2300-1527D/GB

A

A

A

Think future. Switch to green.

Think future. Switch to green.

Rückenbreite bis 10 mm (1 Blatt = 0,106 mm für XBS)

Summary of Contents for ZB12 Series

Page 1: ... Bonn E Mail info moeller net Internet www moeller net 2002 by Moeller GmbH Subjekt to alteration AWB2300 1527D GB Doku Doku Eb 05 05 Printed in the Federal Republic of Germany 0x 05 Article No 284910 4 patpks v y Rückentext Hardware und Projektierung Hardware and Engineering 05 05 AWB2300 1527D GB A A A Think future Switch to green Think future Switch to green Rückenbreite bis 10 mm 1 Blatt 0 106...

Page 2: ...gt oder verbreitet werden Änderungen vorbehalten Gedruckt auf Papier aus chlor und säurefrei gebleichtem Zellstoff All brand and product names are trademarks or registered trademarks of the owner concerned 1st published 2004 edition date 02 04 2nd edition 05 2005 See revision protocol in the About this manual chapter Moeller GmbH Bonn Author Wolfgang Nitschky Editor Heidrun Riege Translator David ...

Page 3: ... nur im eingebauten Zustand betrieben und bedient werden Before commencing the installation Disconnect the power supply of the device Ensure relosing interlock that devices cannot be accidentally restarted Verify isolation from the supply Connect to earth and short circuit Cover or fence off neighbouring live parts Follow the installation instructions AWA included with the device Only suitably qua...

Page 4: ... 05 AWB2300 1527D GB Motorschutzrelais ZB12 und ZB32 Überlastüberwachung von EEx e Motoren 1 ZB12 and ZB32 motor protective relays Overload monitoring of EEx e motors 27 Anhang Appendix 53 Überblick Overview ...

Page 5: ... Strombereiche der Motorschutzrelais 7 Temperaturkompensation 9 Phasenausfall 9 Wiedereinschaltung 10 Testfunktion 11 2 Projektierung 13 Überlastüberwachung von Motoren im EEx e Bereich 13 Einstellung der Überstromschutzeinrichtung 13 Kurzschlussschutz der Motorschutzrelais 14 Zulassungen 17 3 Installation 19 Hinweise zur Installation 19 Geräte montieren 21 4 Geräte betreiben 25 Einstellungen 25 R...

Page 6: ...B12 0 16 und and ZB32 0 16 56 ZB12 0 24 und and ZB32 0 24 58 ZB12 0 4 und and ZB32 0 4 60 ZB12 0 6 und and ZB32 0 6 62 ZB12 1 und and ZB32 1 64 ZB12 1 6 und and ZB32 1 6 66 ZB12 2 4 und and ZB32 2 4 68 ZB12 4 und and ZB32 4 70 ZB12 6 und and ZB32 6 72 ZB12 10 und and ZB32 10 74 ZB12 12 76 ZB12 16 78 ZB32 16 80 ZB32 24 82 ZB32 32 84 Konformitätserklärung Declaration of Conformity 86 ...

Page 7: ... und wartet Abkürzungen und Symbole In diesem Handbuch werden Abkürzungen und Symbole eingesetzt die folgende Bedeutung haben X zeigt Handlungsanweisungen an EEx e Zündschutzart Erhöhte Sicherheit PTB Physikalisch Technische Bundesanstalt Zerti fizierungsstelle für Geräte im EEx Bereich NM Niedrigster möglicher Einstellstrom HM Höchster möglicher Einstellstrom h macht Sie aufmerksam auf interessan...

Page 8: ...ende Änderungsprotokoll j Warnung warnt vor schweren Sachschäden und schweren Verletzungen oder Tod Redaktions datum Seite Stichwort neu Ände rung ent fällt 05 05 6 Abschnitt Direktanbau j 8 Tabelle 1 Strombereiche ZB12 Relais j 9 Abschnitt Temperaturkompensation j 15 Tabelle 3 ZB12 in Direktanbau j 16 Tabelle 4 ZB32 in Direktanbau oder Einzelaufstellung j 21 Tabelle 5 Direktanbau j 54 Tabelle 9 W...

Page 9: ...Funken und Lichtbögen an Motoren bei denen dies im normalen Betrieb nicht auftritt verhindert Die Motorschutzgeräte hierfür die sich selber nicht im EEx e Bereich befinden müssen durch eine akkreditierte Zulassungsstelle zertifiziert sein Die Richtlinie 94 9 EG ATEX 100a zur Angleichung der Rechtsvorschriften der Mitgliedsstaaten für Geräte und Schutzsysteme zur bestimmungsmäßigen Verwendung in ex...

Page 10: ...ZB12 und ZB32 sind als Direktanbau an die Schütze DIL einsetzbar Direktanbau Zusätzlich ist das Relais ZB32 in Kombination mit einer Einzelaufstellung einzeln einsetzbar Einzelaufstellung Bei einer Überlastauslösung schalten die Hilfsschalter 95 96 und 97 98 um und unterbrechen den Steuerstromkreis des zugehörigen Leistungsschützes Sie schalten so indirekt den Stromfluss des zu überwachenden Motor...

Page 11: ...ütz M1 Motor Strombereiche der Motorschutzrelais Die Z Relais werden mit Hilfe einer Strom Einstellscheibe auf den Motornennstrom eingestellt Mit verschiedenen Typen können Motoren von 0 1 bis 32 A Motornennstrom überwacht werden M1 M U V W F2 F1 L1 L2 L3 Q11 2 4 6 2 4 6 97 97 95 96 1 3 5 PE 3 L1 Q11 1 95 96 21 22 13 14 F2 0 S11 I 13 14 Q11 A1 A2 Q11 N F0 ...

Page 12: ... ZB12 1 0 0 6 bis 1 0 ZB12 1 6 1 0 bis 1 6 ZB12 2 4 1 6 bis 2 4 ZB12 4 2 4 bis 4 0 ZB12 6 4 0 bis 6 0 ZB12 10 6 0 bis 10 ZB12 12 9 bis 12 ZB12 16 12 bis 16 Typ Strombereich I A ZB32 0 16 0 1 bis 0 16 ZB32 0 24 0 16 bis 0 24 ZB32 0 4 0 24 bis 0 4 ZB32 0 6 0 4 bis 0 6 ZB32 1 0 0 6 bis 1 0 ZB32 1 6 1 0 bis 1 6 ZB32 2 4 1 6 bis 2 4 ZB32 4 2 4 bis 4 0 ZB32 6 4 0 bis 6 0 ZB32 10 6 0 bis 10 ZB32 16 10 bi...

Page 13: ...d ZB32 sind phasenausfallemp findlich Die Auslenkung aller drei Bimetalle wirkt auf eine Auslösebrücke die bei Erreichen des Grenzwertes einen Sprungschalter umschaltet Gleichzeitig verschieben alle drei Bimetalle die Differenzialbrücke Wird bei einem Phasenaus fall ein Bimetall weniger ausgelenkt bleibt die Differential brücke zurück und der Weg wird in zusätzlichen Auslöseweg umgewandelt so dass...

Page 14: ...In der Stellung Automatik fallen die Kontakte nach der Abkühlung der Bimetalle automatisch zurück in der Hand stellung muss die Auslösung vor Ort am Motorschutzrelais quittiert werden h Soll mit einem ZB12 oder ZB32 Relais ein Wechselstrom motor oder ein Gleichstrommotor überwacht werden muss der Strom über alle drei Strombahnen geführt werden um Frühauslösungen zu vermeiden j Warnung Für den Expl...

Page 15: ...taste öffnet den Öffner 95 96 Nach dem Loslassen fällt der Öffner wieder zurück Diese Funktion kann zum manuellen Ausschalten des Motors genutzt werden Das Ziehen der Testtaste führt zur Auslösung des Motor schutzrelais Der Öffner 95 96 öffnet und der Schließer 97 98 schließt Nach dem Loslassen der Testtaste muss das Motorschutzrelais wie nach einer Auslösung zurück gesetzt werden a Abschnitt Wied...

Page 16: ...12 05 05 AWB2300 1527D GB ...

Page 17: ... jedoch noch nicht sicher Sie erlangen die Explosionssicherheit erst durch zusätzliche Maßnahmen bei der Installation durch zweckentsprechende Auswahl und Einsatzbedingungen PTB Prüfregeln u a durch das Zusammenschalten mit einer richtig bemessenen und eingestellten Überstromschutzeinrichtung Einstellung der Über stromschutzeinrichtung j Warnung Die stromabhängige Schutzeinrichtung muss so ausge w...

Page 18: ...otorschutzrelais Der Kurzschlussschutz der Motorschutzrelais wird durch Sicherungen realisiert Bei Direktanbau an ein Schütz wird die Vorsicherung des Schützes für die entsprechende Zuord nungsart mit berücksichtigt 1 0 1 0 2 0 4 0 6 0 8 1 2 4 6 8 10 20 40 1 2 4 6 8 10 2 3 4 5 6 7 8 9 10 J min s N 1 i Vorsicht Zum Schutz von EEx e Motoren ist nur die Zuordnungsart 2 zulässig ...

Page 19: ...nbau Schütz Sicherung gG gL A Bemessungs Zuordnungsart 1 1 Zuordnungsart 2 1 kurzschlussstrom Iq kA ZB12 0 16 DILM7 DILM9 DILM12 DILM15 25 0 5 100 ZB12 0 24 1 ZB12 0 4 2 ZB12 0 6 4 ZB12 1 0 4 ZB12 1 6 6 ZB12 2 4 10 ZB12 4 16 ZB12 6 20 ZB12 10 50 25 ZB12 12 50 25 ZB12 16 50 25 1 nach IEC EN 60947 ...

Page 20: ...tz Sicherung gG gL A Bemessungs Zuordnungsart 1 1 Zuordnungsart 2 1 kurzschlussstrom Iq kA ZB32 0 16 DILM17 DILM25 DILM32 25 0 5 100 ZB32 0 24 1 ZB32 0 4 2 ZB32 0 6 4 ZB32 1 0 4 ZB32 1 6 6 ZB32 2 4 10 ZB32 4 16 ZB32 6 20 ZB32 10 50 25 ZB32 16 63 35 ZB32 24 100 35 ZB32 32 125 63 1 nach IEC EN 60947 ...

Page 21: ...EG ATEX 100a zum Schutz von EEx e Motoren Außerdem können nach EN 50281 1 1 und EN 50281 1 2 Motoren in den Zonen 21 und 22 Bereiche mit brennbarem Staub geschützt werden Die Motorabgangsverdrahtung ist nach IEC EN 60947 1 Tabelle 9 auszuführen ZB12 PTB 04 ATEX 3022 ZB32 PTB 04 ATEX 3022 Die Relais sind nach UL und CSA für die USA und Kanada approbiert Weitere Approbationen bestehen für c U s Chin...

Page 22: ...18 05 05 AWB2300 1527D GB ...

Page 23: ...chutz ist nur ein manuelles Rück setzen Einschalten nach Abkühlung der Bimetalle oder ein automatisches Zuschalten über eine Steuerungsverriege lung zum Motor bzw zur elektrischen Maschine zulässig Rücksetzungen dürfen manuell vor Ort oder durch geschultes Personal in der Leitwarte vorgenommen werden j Warnung Insbesondere darf bei EEx e Anwendungen nach Ausfall der Steuerspannung und Spannungsrüc...

Page 24: ...ederanlauf F1 Sicherung F2 Motorschutzrelais K1M Leistungsschütz M1 Motor Die Selbsthaltung des Leistungsschützes K1M verhindert einen automatischen Wiederanlauf M1 M U V W F2 F1 L1 L2 L3 Q11 2 4 6 2 4 6 97 97 95 96 1 3 5 PE 3 L1 Q11 1 95 96 21 22 13 14 F2 0 S11 I 13 14 Q11 A1 A2 Q11 N F0 ...

Page 25: ...ination mit der Einzelauf stellung einzeln eingesetzt werden Tabelle 5 Direktanbau Tabelle 6 Einzelaufstellung X Montieren Sie die Geräte wie in den nachfolgenden Abbildungen angegeben Abbildung 8 Montage ZB12 ZB32 Schütz Motorschutzrelais DILM7 DILM9 DILM12 DILM15 ZB12 DILM17 DILM25 DILM32 ZB32 Motorschutzrelais Einzelaufstellung ZB32 ZB32 XEZ ZB32 XEZ ZB32 ZB12 ZB32 ...

Page 26: ...auf einer Hutschiene oder direkt auf der Montageplatte montiert werden Tabelle 7 Maße zur Montage X Verdrahten Sie die Motorleitungen Abbildung 9 Hauptstromverdrahtung Folgende Leitungsquerschnitte sind möglich ZB32 XEZ Bohrmaße B x H mm 35 x 75 Schraube mm 2 x M4 x 12 1h H 3 ...

Page 27: ...hnen Hilfsstrom bahnen ZB12 ZB32 95 96 97 98 1 x 1 6 1 x 1 6 1 x 0 75 4 mm2 2 x 1 6 2 x 1 6 2 x 0 75 4 1 1 x 1 6 1 x 1 6 1x 0 75 2 5 mm2 2 x 1 6 2 x 1 6 2x 0 75 2 5 AWG 1 x 14 8 1 x 14 8 1 x 18 12 2 x 14 8 2 x 14 8 2 x 18 12 Anzugsdreh moment Nm 1 8 1 8 1 2 1 Aderendhülse nach DIN 46228 ...

Page 28: ...24 05 05 AWB2300 1527D GB ...

Page 29: ...uf A und einer Handrücksetzung H zu wählen Abbildung 10 Schaltmöglichkeiten mit Wahlknopf Reset Die Stellung H verhindert einen automatischen Wiederan lauf und ist werksseitig bei den Motorschutzrelais vorge wählt In der Stellung H muss das Relais nach einer Auslösung händisch durch Drücken dieses Wahlknopfes zurückgesetzt werden i Vorsicht Bei einem kühlen Aufstellungsort des Motorschutzrelais z ...

Page 30: ...aste Test Ein Drücken der Taste hat das Öffnen des Hilfskontaktes 95 96 zur Folge und kann zum Abschalten des Schützes genutzt werden Im stromlosen Zustand kann durch das Drücken der Taste die Funktion beider Hilfsschalter getestet werden TEST NC 95 NC 96 NO 97 NO 98 OFF j Warnung Funktionsuntüchtige Geräte dürfen nicht geöffnet und repariert werden Sie müssen von Fachpersonal ausge tauscht werden...

Page 31: ...lic release 32 Current ranges of the motor protective relays 33 Temperature compensation 35 Phase loss 35 Reset 36 Test function 37 2 Configuration 39 Monitoring overload of motors in the EEx e area 39 Adjusting the overload current protection 39 Short circuit protection of the motor protective relays 40 Approvals 43 3 Installation 45 Notes on installation 45 Mounting the devices 47 4 Operating th...

Page 32: ... ZB12 0 16 und and ZB32 0 16 56 ZB12 0 24 und and ZB32 0 24 58 ZB12 0 4 und and ZB32 0 4 60 ZB12 0 6 und and ZB32 0 6 62 ZB12 1 und and ZB32 1 64 ZB12 1 6 und and ZB32 1 6 66 ZB12 2 4 und and ZB32 2 4 68 ZB12 4 und and ZB32 4 70 ZB12 6 und and ZB32 6 72 ZB12 10 und and ZB32 10 74 ZB12 12 76 ZB12 16 78 ZB32 16 80 ZB32 24 82 ZB32 32 84 Konformitätserklärung Declaration of Conformity 86 ...

Page 33: ...used in this manual have the following meaning X indicates actions to be taken EEx e Increased safety type of protection PTB Physikalisch Technische Bundesanstalt German Federal Testing Laboratory Accredited certification authority for devices operated in EEx e areas NM Lowest possible setup current HM Highest possible setup current h Draws our attention towards interesting tips and additional inf...

Page 34: ...a chapter Modification index j Warning Warns of the risk of heavy material damage and of serious or lethal injury Edition date Page Subject New Modi fied Omitted 05 05 32 section Direct mounting j 34 table 1 ZB12 relay current ranges j 35 section Temperature compensation j 41 table 3 ZB12 direct mounting j 42 table 4 Direct mounting or individual installation of the ZB32 j 47 table 5 Direct mounti...

Page 35: ... which usually does not occur under normal operating conditions The motor protective equipment used for this is operated at a location separate from the EEx e area and must be certified by an accredited certification authority The guidelines on the application of Directive 94 9 EC ATEX 100a on the approximation of the laws of the Member States concerning equipment and protective systems intended f...

Page 36: ...AC current The ZB12 and ZB32 overload relays can be mounted directly on the DIL contactors Direct mounting Furthermore the ZB32 relay can be used individually in combination with an individual mounting Individual mounting In the event of overload tripping the auxiliary contacts 95 96 and 97 98 change over and disconnect the control voltage circuit from the corresponding contactor relay and Motor p...

Page 37: ...or protective relay K1M Motor contactor M1 Motor Current ranges of the motor protective relays The rated motor current is set on the Z relays by means of a current setting dial The various types can be used to monitor motors operating at a rated current of 0 1 to 32 A M1 M U V W F2 F1 L1 L2 L3 Q11 2 4 6 2 4 6 97 97 95 96 1 3 5 PE 3 L1 Q11 1 95 96 21 22 13 14 F2 0 S11 I 13 14 Q11 A1 A2 Q11 N F0 ...

Page 38: ... to 0 6 ZB12 1 0 0 6 to 1 0 ZB12 1 6 1 0 to 1 6 ZB12 2 4 1 6 to 2 4 ZB12 4 2 4 to 4 0 ZB12 6 4 0 to 6 0 ZB12 10 6 0 to 10 ZB12 12 9 to 12 ZB12 16 12 to 16 Type Current range I A ZB32 0 16 0 1 to 0 16 ZB32 0 24 0 16 to 0 24 ZB32 0 4 0 24 to 0 4 ZB32 0 6 0 4 to 0 6 ZB32 1 0 0 6 to 1 0 ZB32 1 6 1 0 to 1 6 ZB32 2 4 1 6 to 2 4 ZB32 4 2 4 to 4 0 ZB32 6 4 0 to 6 0 ZB32 10 6 0 to 10 ZB32 16 10 to 16 ZB32 ...

Page 39: ...he deflecting action of all three bimetallic releases is directed towards a tripping bridge that switches over a quick break switch when the limit value is reached At the same time all three bimetallic releases shift the differential bridge If the path of action of one of the bimetallic releases is reduced due to a phase loss the differential bridge is retarded and the distance is converted into a...

Page 40: ...tacts automatically fall back after the bimetallic releases have cooled down whereas in manual mode the tripping must be acknowledged locally on the motor protective relay h When a ZB12 or ZB32 relay is to be used for monitoring an AC or DC motor the current must flow across all three current paths in order to avoid early tripping j Warning To ensure explosion proof operation the motor protective ...

Page 41: ...act NC 95 96 The open contact will return to the closed position as soon as the button is released This function can also be used to switch off the motor manually Pulling the button will trip the motor protective relay The break contact 95 96 opens and the make contact 97 98 closes After the test button is released the motor protective relay must be reset in the same way as after a normal tripping...

Page 42: ...38 05 05 AWB2300 1527D GB ...

Page 43: ...er since EEx e motors are not intrinsically safe explosion safety is only achieved by taking special measures during installation and by selecting appropriate operating conditions PTB testing regulations e g by a combination of the circuit with a correctly rated and set overload current protection Adjusting the overload current protection j Warning The selected current overload protection system m...

Page 44: ...ective relays The motor protective relays are short circuit protected by means of fuses When the relay is mounted directly onto a contactor relay the corresponding primary fuse of the contactor relay is taken into account accordingly 1 0 1 0 2 0 4 0 6 0 8 1 2 4 6 8 10 20 40 1 2 4 6 8 10 2 3 4 5 6 7 8 9 10 J min s N 1 i Caution Only co ordination type 2 is permissible for the protection of EEx e mo...

Page 45: ...ntactor relay Fuse gG gL A Rated short circuit Type of assignment 1 1 Type of assignment 2 1 current Iq kA ZB12 0 16 DILM7 DILM9 DILM12 DILM15 25 0 5 100 ZB12 0 24 1 ZB12 0 4 2 ZB12 0 6 4 ZB12 1 0 4 ZB12 1 6 6 ZB12 2 4 10 ZB12 4 16 ZB12 6 20 ZB12 10 50 25 ZB12 12 50 25 ZB12 16 50 25 1 to IEC EN 60947 ...

Page 46: ...of the ZB32 Contactor relay Fuse gG gL A Type of assignment 1 1 Type of assignment 2 1 ZB32 0 16 DILM17 DILM25 DILM32 25 0 5 100 ZB32 0 24 1 ZB32 0 4 2 ZB32 0 6 4 ZB32 1 0 4 ZB32 1 6 6 ZB32 2 4 10 ZB32 4 16 ZB32 6 20 ZB32 10 50 25 ZB32 16 63 35 ZB32 24 100 35 ZB32 32 125 63 1 to IEC EN 60947 ...

Page 47: ...0a directive for the protection of EEx e motors Furthermore motors in zones 21 and 22 areas with combustible dusts can be protected conform to EN 50281 1 1 and EN 50281 1 2 The motor outgoer wiring must be implemented conform to IEC EN 60947 1 table 9 ZB12 PTB 04 ATEX 3022 ZB32 PTB 04 ATEX 3022 The relays are approved by UL and CSA for the USA and Canada Further approvals exist for c U s China 010...

Page 48: ...44 05 05 AWB2300 1527D GB ...

Page 49: ... operation the motor protective relay may only be reset switched on manually or automatically via a control interlock circuit for the motor or electrical machinery after the bimetallic release has cooled down A manual reset may be carried out by trained personnel locally or in the control room j Warning Particularly in EEx e applications an automatic restart must be prevented after an interruption...

Page 50: ...ic restart F1 Fuse F2 Motor protective relay K1M Contactor relay M1 Motor The latching function of the K1M contactor relay prevents an automatic restart M1 M U V W F2 F1 L1 L2 L3 Q11 2 4 6 2 4 6 97 97 95 96 1 3 5 PE 3 L1 Q11 1 95 96 21 22 13 14 F2 0 S11 I 13 14 Q11 A1 A2 Q11 N F0 ...

Page 51: ...ally be used in combination with an individual mounting Table 5 Direct mounting Table 6 Individual installation X Mount the devices as shown in the figures below Figure 8 Mounting ZB12 ZB32 Contactor relay Motor protective relay DILM7 DILM9 DILM12 DILM15 ZB12 DILM17 DILM25 DILM32 ZB32 Motor protective relay Individual mounting ZB32 ZB32 XEZ ZB32 XEZ ZB32 ZB12 ZB32 ...

Page 52: ...B32 XEZ can be mounted on a top hat rail or directly on a mounting plate Table 7 Mounting dimensions X Wire the motor cables Figure 9 Mains wiring The following conductor cross sections can be used ZB32 XEZ Bore dimensions W x H mm 35 x 75 Screw mm 2 x M4 x 12 1h H 3 ...

Page 53: ...rcuit Auxiliary voltage circuit ZB12 ZB32 95 96 97 98 1 x 1 6 1 x 1 6 1 x 0 75 4 mm2 2 x 1 6 2 x 1 6 2 x 0 75 4 1 1 x 1 6 1 x 1 6 1x 0 75 2 5 mm2 2 x 1 6 2 x 1 6 2x 0 75 2 5 AWG 1 x 14 8 1 x 14 8 1 x 18 12 2 x 14 8 2 x 14 8 2 x 18 12 Tightening torque N m 1 8 1 8 1 2 1 Ferrule to DIN 46228 ...

Page 54: ...50 05 05 AWB2300 1527D GB ...

Page 55: ... of the Reset selector button Figure 10 Switching options of the reset selector button The factory set position H on the motor protective relay prevents automatic restarts In position H the relay must be reset manually after it has tripped by pressing the selector button i Caution If the overload relay is installed at a cool location e g 5 C and the motor is installed at a warm motor location e g ...

Page 56: ...options of the test button The auxiliary contact 95 96 is opened by pressing the button and can thus be used to switch off the contactor relay The function of both auxiliary contacts can be tested in current less state by pressing the button TEST NC 95 NC 96 NO 97 NO 98 OFF j Warning Faulty devices may not be opened for repairs and may only be replaced suitably qualified personnel ...

Page 57: ...e zu den jeweiligen Typen sind der nachfolgenden Tabelle 9 zu entnehmen For information on the assignment of values to the relevant types please refer to Tabelle 9 Uimp 6000 V Uimp 6000 V Ith 6 A Ue 690 V h Normal 97 95 98 96 97 95 98 96 Test A F 97 95 98 96 max A gL 1 2 AC 15 Ue 220 240 95 96 Ie 1 5 97 98 Ie 1 5 380 415 500Vh 0 9 0 8 A 0 5 0 5 A IEC EN 60947 C D II 2 GD PTB 04 ATEX 3022 0102 A014...

Page 58: ...B12 1 6 1 1 6 A 25 6 ZB122 4 1 6 2 4 A 25 10 ZB12 4 2 4 4 A 25 16 ZB12 6 4 6 A 25 20 ZB12 10 6 10 A 50 25 ZB12 12 9 12 A 50 25 ZB12 16 12 16 A 50 25 ZB32 0 16 0 1 0 16 A 25 0 5 ZB32 0 24 0 16 0 24 A 25 1 ZB32 0 4 0 24 0 4 A 25 2 ZB32 0 6 0 4 0 6 A 25 4 ZB32 1 0 6 1 A 25 4 ZB32 1 6 1 1 6 A 25 6 ZB322 4 1 6 2 4 A 25 10 ZB32 4 2 4 4 A 25 16 ZB32 6 4 6 A 25 20 ZB32 10 6 10 A 50 25 ZB32 16 10 16 A 63 3...

Page 59: ...Auslösekennlinien Tripping characteristics 55 05 05 AWB2300 1527D GB Auslösekennlinien Tripping characteristics ...

Page 60: ... Range 0 1 0 16 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 23 17 5 21 14 7 2 x I 5 5 4 6 5 2 4 0 ...

Page 61: ...Auslösekennlinien Tripping characteristics 57 05 05 AWB2300 1527D GB Abbildung Figure 13 ZB12 0 16 und and ZB32 0 16 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 62: ... Range 0 16 0 24 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 21 15 21 13 5 7 2 x I 5 1 4 5 1 3 6 ...

Page 63: ...Auslösekennlinien Tripping characteristics 59 05 05 AWB2300 1527D GB Abbildung Figure 14 ZB12 0 24 und and ZB32 0 24 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 64: ...ange 0 24 0 4 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 23 5 18 22 13 5 7 2 x I 5 9 4 8 5 5 4 0 ...

Page 65: ...Auslösekennlinien Tripping characteristics 61 05 05 AWB2300 1527D GB Abbildung Figure 15 ZB12 0 4 und and ZB32 0 4 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 66: ...ange 0 4 0 6 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 27 19 5 25 15 5 7 2 x I 6 5 5 4 6 2 4 6 ...

Page 67: ...Auslösekennlinien Tripping characteristics 63 05 05 AWB2300 1527D GB Abbildung Figure 16 ZB12 0 6 und and ZB32 0 6 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 68: ...ange 0 6 1 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 29 4 22 26 15 7 2 x I 7 3 5 9 6 5 4 6 ...

Page 69: ...Auslösekennlinien Tripping characteristics 65 05 05 AWB2300 1527D GB Abbildung Figure 17 ZB12 1 und and ZB32 1 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 70: ...h Range 1 1 6 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 29 20 27 16 7 2 x I 6 9 5 5 6 5 4 4 ...

Page 71: ...Auslösekennlinien Tripping characteristics 67 05 05 AWB2300 1527D GB Abbildung Figure 18 ZB12 1 6 und and ZB32 1 6 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 72: ...ange 1 6 2 4 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 28 5 19 25 15 3 7 2 x I 6 8 5 3 6 3 4 7 ...

Page 73: ...Auslösekennlinien Tripping characteristics 69 05 05 AWB2300 1527D GB Abbildung Figure 19 ZB12 2 4 und and ZB32 2 4 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 74: ...nge 2 4 4 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 32 1 24 30 17 9 7 2 x I 7 8 6 5 7 3 5 2 ...

Page 75: ...Auslösekennlinien Tripping characteristics 71 05 05 AWB2300 1527D GB Abbildung Figure 20 ZB12 4 und and ZB32 4 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 76: ...Range 4 6 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 32 5 24 5 30 19 2 7 2 x I 7 4 6 6 9 5 ...

Page 77: ...Auslösekennlinien Tripping characteristics 73 05 05 AWB2300 1527D GB Abbildung Figure 21 ZB12 6 und and ZB32 6 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 78: ... Range 6 10 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 33 5 23 7 31 19 7 2 x I 7 5 3 6 2 4 4 ...

Page 79: ...Auslösekennlinien Tripping characteristics 75 05 05 AWB2300 1527D GB Abbildung Figure 22 ZB12 10 und and ZB32 10 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 80: ... A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 30 7 18 8 27 2 15 7 7 2 x I 6 1 4 1 5 6 3 6 ...

Page 81: ...Auslösekennlinien Tripping characteristics 77 05 05 AWB2300 1527D GB Abbildung Figure 23 ZB12 12 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 82: ...12 16 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 30 24 29 19 7 2 x I 4 3 3 6 4 1 3 ...

Page 83: ...Auslösekennlinien Tripping characteristics 79 05 05 AWB2300 1527D GB Abbildung Figure 24 ZB12 16 1 0 1 1 10 100 1000 2 3 4 5 6 7 8 9 10 b c d a ...

Page 84: ... 16 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 30 22 28 16 4 7 2 x I 4 1 3 2 3 8 2 4 ...

Page 85: ...Auslösekennlinien Tripping characteristics 81 05 05 AWB2300 1527D GB Abbildung Figure 25 ZB32 16 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 86: ... 24 A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 34 5 24 5 30 19 7 2 x I 6 3 4 9 5 6 4 ...

Page 87: ...Auslösekennlinien Tripping characteristics 83 05 05 AWB2300 1527D GB Abbildung Figure 26 ZB32 24 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 88: ... A NM HM Umgebungstemperatur Ambient temperature 20 C Auslöseklasse Tripping class 10 A Toleranzbereich Tolerance range g 20 Einstellung Setting Auslösezeit Tripping time t s NM HM 3 phase a 2 phase c 3 phase b 2 phase d 3 x I 30 2 21 8 26 6 17 8 7 2 x I 6 1 4 7 5 4 3 9 ...

Page 89: ...Auslösekennlinien Tripping characteristics 85 05 05 AWB2300 1527D GB Abbildung Figure 27 ZB32 32 1 0 1 0 5 1 5 10 50 100 500 1000 2 3 4 5 6 7 8 9 10 a c d b ...

Page 90: ...Anhang Appendix 86 05 05 AWB2300 1527D GB Konformitätserklärung Declaration of Conformity ...

Page 91: ... Bonn E Mail info moeller net Internet www moeller net 2002 by Moeller GmbH Subjekt to alteration AWB2300 1527D GB Doku Doku Eb 05 05 Printed in the Federal Republic of Germany 09 05 Article No 284910 4 patpks v y Rückentext Hardware und Projektierung Hardware and Engineering 05 05 AWB2300 1527D GB A A A Think future Switch to green Think future Switch to green Rückenbreite bis 10 mm 1 Blatt 0 106...

Reviews: