VOLTAGE RELAY  PNM-10

 

INSTRUCTION MANUAL

APPEARANCE

ver. 0.4.2 _ 2006.06.26_13:00

FEATURES

TECHNICAL PARAMETERS

DESCRIPTION

PNM - 10

Input (supply) terminals: L, N

Input rated voltage: 230 V~

Input voltage tolerance: from -15 to +10 %

Nominal frequency: 50 / 60 Hz

Rated power consumption:  35 mA

Voltage value control indicator: LED green

Power/relay supply indicator and “soft net”: LED red

Voltage threshold adjustment: 2x rotary potentiometer

Voltage threshold adjustment range U

min

: from 170 to 225 V

Voltage threshold adjustment range U

max

: from 235 to 290 V

Switch off time adjustment t

off

: from 0 to 12 s rotary potentiometer

Time/Voltage measure accuracy:  ±1,5 / ±5 %

Switch off time after “soft net” detection: 10 min (LED red pulses)

Output relay parameters: 1NO/NC - 10 A / 250 V AC1 2500 VA

Number of terminal clamps: 5

Section of connecting cables: from 0,2 to 2,50 mm

2

Ambient temperature range: from -20 to +60 

o

C

Operating position: free

Mounting: TH35 rail (PN-EN 60715)

Protection degree: IP20 (PN-EN 60529)

Protective class: II

Overvoltage category: II

Pollution degree: 2

Rated impulse withstand voltage: 2 kV (PN-EN 61000-4-5)

Dimensions (height / width / depth): monomodular (17,5 mm) 90x17,5x66 mm

Weight: 73 g

Reference standards: PN-EN 60730-1; PN-EN 60730-2-1;

PN-EN 61000-4-2,3,4,5,6,11

ی  It is used to protect one phase out-

put (load) from voltage drop,

ی  voltage value control indicator,
ی  power/relay supply indicator,
ی  minimum  value  adjustment  (170  - 

225 V) and maximum (235 - 290 V) 

voltage,

ی  switch  off  time  delay  adjustment 

(0-12 seconds),

ی  “soft net” effect detection,
ی  voltage relay output - 1 change over 

contact (NO/NC) max 10 A capacity,

ی  monomodular casing,
ی  TH-35 DIN rail installation.

The  device  is  used  to  control  the 

voltage  value  in  one-phase  net  in  or-
der  to  secure  the  output  from  voltage 
increase and decrease below the preset 
minimum and maximum values. The sy-
stem is equipped with switching off time 
regulation. The system detects the “soft 
net” effect switching of the output (load) 
for 10 minutes.

Zakład Mechaniki i Elektroniki 

ZAMEL 

sp.j.

J.W. Dzida, K. Łodzińska

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamel.pl, 

e-mail:

 [email protected]

Output  (load) 

Voltage  value 

Input supply terminals (L)

Input supply terminals (N)

Minimum voltage 

Maximum voltage 

Power/relay supply indicator 

“soft net” effect

relay terminals (11, 12, 14)

Switch  off  delay 
time threshold 

value adjustment

value adjustment

control indicator 

The  device  is  desig-

ned  for  one-phase 

installation  and  must 

be  installed  in  accor-

dance  with  standards 

valid in a particular co-

untry. The device sho-

uld be connected according to the details 

included in this operating manual. Instal-

lation, connection and control should be 

carried out by a qualified electrician staff, 

who  act  in  accordance  with  the  service 

manual and the device functions. Disas-

sembling  of  the  device  is  equal  with  a 

loss of guarantee and can cause electric 

shock. Before installation make sure the 

connection cables are not under voltage. 

The cruciform head screwdriver 3,5 mm 

should be used to instal the device. Im-

proper transport, storage, and use of the 

device  influence  its  wrong  functioning. 

It is not advisable to instal the device in 

the following cases: if any device part is 

missing or the device is damaged or de-

formed. In case of improper functioning 

of the device contact the producer.

CAUTION

Reviews: