Earth Leakage Relay

User Manual

ME-ELR-DD

• 

Adjustable sensitivity

• 

Adjustable time delay

• 

LED Status indicators

• 

Leakage current indication

• 

Remote test and reset switching

• 

DIN rail mounting

• 

Current measurement based on fundamental frequency, prevents nuisance tripping

• 

Dial adjustment for ease of use

• 

Robust casing protects the unit from external interference

• 

Serial Number Tracked

Features

The ME-ELR-DD are microprocessors based earth leakage relays designed for measure the 
low-level leakage or unbalanced currents due to insulation loss in conductors or equipment to be 
protected. A zero phase current transformer is used to sense the leakage current. All conductors 
of the circuit to be protected shall go through the ME-T.

For better fault preventive control of the system or equipment, ME-ELR-DD comes with a pre-
fault alarm contact and a positive safety contact. The pre-fault alarm contact is energized when-
ever the leakage current exceed 50% of the sensitivity setting, I n. The positive safety contact is 
energized if the relay is power up and function correctly.

Description

Applications

Technical Data

• 

Industrial equipment protection

• 

Personnel protection from Earth Leakage 
faults

• 

Suitable for low voltage distribution
protection

Auxiliary Supply

ME-ELR-DD-110A

94 ~ 127 VAC

ME-ELR-DD-24A

21 ~ 28 VDC

Rated frequency

50Hz

VA rating

3 VA typical

Setting Ranges

Sensitivity adjustment

30mA, 50mA,
0.10A – 1.00A (Step = 50mA),
1.00A – 5.0A (Step = 1.00A)

Delay time adjustment

0.05s - 0.5s (Step = 0.05s)

Record

Fault record

3 latest tripped fault currents

Storage

Non-volatile memory

Input

Remote reset

N.O. dry contact

Outputs

Trip contact

5A / 250V AC1

Positive safety contact

5A / 250V AC1

Pre-fault alarm contact

5A / 250V AC1

Contact Specification

Contact arrangement

3 latest tripped fault currents

Contact material

Non-volatile memory

Expected electrical life

100,000 at rated current

Expected mechanical life

5x10

6

 operations

Summary of Contents for ME-ELR-DD

Page 1: ... comes with a pre fault alarm contact and a positive safety contact The pre fault alarm contact is energized when ever the leakage current exceed 50 of the sensitivity setting I n The positive safety contact is energized if the relay is power up and function correctly Description Applications Technical Data Industrial equipment protection Personnel protection from Earth Leakage faults Suitable for...

Page 2: ...cators display the status of the system as follow Indicators Pre fault alarm Red indicator Time delay Red indicator Leakage trip 7 segment display red indicator ME T fault 7 segment display red indicator Real time leakage current 7 segment display Zero Phase Current Transformer To operate with Mikro s ME T series of current transformer Delay time adjustment 0 05s 0 5s Step 0 05s Mechanical Mountin...

Page 3: ...Integral Trip Test Press the TEST button to perform an integral test on the relay ranging from analog sensing circuitry to output contact s of the relay as well as the relay indicators and display b Trip Reset Press the RESET button to reset the relay when tripped c CT Fault Press the RESET button to reset the relay after fixing the ME T connection error No reset function is carry out if the fault...

Page 4: ...r fixing the ME T connec tion error To reset the relay make a connection between terminals 4 and 5 of the relay Output Contact a Trip Contact This is the latching type contact It is energized either relay tripped due to leakage fault or broken connection between the relay and the ME T b Positive Safety Contact Contact energized when the relay is power up and function correctly with no tripping c P...