4.9.9
Technical data
Table 649:
AFD Technical data
Characteristic
Value
Operation accuracy
±3% of the set value or ±0.01 × I
n
Trip time
Minimum
Typical
Maximum
Operation mode = "Light
+current"
1)2)
9 ms
3)
4 ms
4)
12 ms
3)
6 ms
4)
15 ms
3)
9 ms
4)
Operation mode = "Light
only"
2)
9 ms
3)
4 ms
4)
10 ms
3)
6 ms
4)
12 ms
3)
7 ms
4)
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
1)
Phase pickup value = 1.0 × I
n
, current before fault = 2.0 × set
Phase pickup value, f
n
= 50 Hz, fault with
nominal frequency, results based on statistical distribution of 200 measurements
2) Includes the delay of the heavy-duty output contact
3) Normal power output
4) High-speed output
4.9.10
Technical revision history
Table 650:
AFD Technical revision history
Technical revision
Change
B
Internal Improvement.
4.10
Motor start-up supervision 66/51LRS
4.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Motor start-up supervision
STTPMSU
Is2t n<
66/51LRS
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
749
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......