Parameter
Values (Range) Unit
Step
Default
Description
High trigger
level
0.00...60.00
pu
0.01
10.00
High trigger
level for the
analog channel
Low trigger
level
0.00...2.00
pu
0.01
0.00
Low trigger
level for the
analog channel
Storage mode
0=Waveform
1=Trend / cycle
1
0
Storage mode
for the analog
channel
1) Recordable values are available only in trend mode. In waveform mode, samples for this signal type are
constant zeroes. However, these signal types can be used to trigger the recorder on limit violations of the
corresponding analog channel.
Table 851:
DFR Non-group binary channel settings
Parameter
Values (Range) Unit
Step
Default
Description
Operation
1=Enable
5=Disable
1
5=Disable
Binary channel
is enabled or
disabled
Level trigger
mode
1=Positive or
Rising
2=Negative or
Falling
3=Both
4=Level trigger
off
1
1=Rising
Level trigger
mode for the
binary channel
Storage mode
0=Waveform
1=Trend / cycle
1
0
Storage mode
for the binary
channel
Channel id text
0 to 64
characters,
alphanumeric
DR binary
channel X
Identification
text for the
analog channel
used in the
COMTRADE
format
Table 852:
DFR Control data
Parameter
Values (Range) Unit
Step
Default
Description
Trig recording
0=Cancel
1=Trig
Trigger the
disturbance
recording
Clear
recordings
0=Cancel
1=Clear
Clear all
recordings
currently in
memory
Section 8
1MAC059074-MB A
Measurement functions
948
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......