4.5.6.10
Technical data
Table 564:
24 Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±3.0% of the set value
Pickup time
1)2)
Frequency change:
Typically 200 ms
Voltage change:
Typically 40 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Trip time accuracy in definite-time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse-time mode
±5.0% of the theoretical value or ±50 ms
1) f
n
= 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
4.5.7
Low-voltage ride-through protection 27RT
4.5.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Low-voltage ride-through protection
LVRTPTUV
U<RT
27RT
4.5.7.2
Function block
V_A_AB
V_B_BC
V_C_CA
27RT
TRIP
BLOCK
PICKUP
V
1
GUID-64E07123-ED63-4775-893C-F3575ED1F7F6 V1 EN
Figure 327:
Function block
4.5.7.3
Functionality
The low-voltage ride-through protection function 27RT is principally a three-phase
undervoltage protection. It differs from the traditional three-phase undervoltage
Section 4
1MAC059074-MB A
Protection functions
658
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......