Measuring mode for phase current and residual current values can be selected with the
Measurement mode
setting parameter.
3.8.3
Settings
Table 44:
FLR settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Trig mode
0=Trip or Pickup
1=Trip only
2=Pickup only
0=Trip or Pickup
Triggering mode
Table 45:
FLR settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Section 3
1MAC059074-MB A
Basic functions
94
615 series ANSI
Technical Manual