Figure 115:
Configurable operating sectors
Table 237:
Momentary per phase direction value for monitored data view
Criterion for per phase direction information
The value for DIR_A/_B/_C
The ANGLE_X is not in any of the defined sectors, or
the direction cannot be defined due too low
amplitude
0 = unknown
The ANGLE_X is in the forward sector
1 = forward
The ANGLE_X is in the reverse sector
2 = backward
(The ANGLE_X is in both forward and reverse
sectors, that is, when the sectors are overlapping)
3 = both
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
239
Technical Manual