Table 757:
MCS-C Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Pickup value
1.0...100.0
%In
0.1
10.0
Pickup value, percentage of the nominal
current
Alarm delay time
100...300000
ms
10
3000
Alarm delay time
Alarm output mode
1=Non-latched
3=Lockout
3=Lockout
Select the operation mode for alarm output
Table 758:
MCS-C Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
Measurement mode
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
6.3.9
Monitored data
Table 759:
MCS-A Monitored data
Name
Type
Values (Range)
Unit
Description
MCS-A
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Table 760:
MCS-B Monitored data
Name
Type
Values (Range)
Unit
Description
MCS-B
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Table 761:
MCS-C Monitored data
Name
Type
Values (Range)
Unit
Description
MCS-C
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 6
1MAC059074-MB A
Supervision functions
860
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......