4.1.7
Loss of load supervision 37M
4.1.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Loss of load supervision
LOFLPTUC
3I<
37M
4.1.7.2
Function block
37
I_A
I_B
I_C
BLOCK
TRIP
PICKUP
GUID-79688824-6B61-45E2-B88B-60560AE5B51C V1 EN
Figure 137:
Function block
4.1.7.3
Functionality
The loss of load supervision function 37M is used to detect a sudden load loss which is
considered as a fault condition.
37M picks up when the current is less than the set limit. It operates with the definite time
(DT) characteristics, which means that the function operates after a predefined trip time
and resets when the fault current disappears.
The function contains a blocking functionality. It is possible to block function outputs, the
definite timer or the function itself, if desired.
4.1.7.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 37M can be described using a module diagram. All the modules in the
diagram are explained in the next sections.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
289
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......