Name
Type
Default
Description
BLK_OPEN
BOOLEAN
0=False
Blocks opening
BLK_CLOSE
BOOLEAN
0=False
Blocks closing
AU_OPEN
BOOLEAN
0=False
Auxiliary open
1)
AU_CLOSE
BOOLEAN
0=False
Auxiliary close
1)2)
TRIP
BOOLEAN
0=False
Trip signal
SYNC_OK
BOOLEAN
1=True
Synchronism-check OK
SYNC_ITL_BYP
BOOLEAN
0=False
Discards ENA_OPEN and ENA_CLOSE interlocking
when TRUE
1) Not available for monitoring
2) Always direct operation
Table 864:
29DS Input signals
Name
Type
Default
Description
POSOPEN
BOOLEAN
0=False
Apparatus open position
POSCLOSE
BOOLEAN
0=False
Apparatus close position
ENA_OPEN
BOOLEAN
1=True
Enables opening
ENA_CLOSE
BOOLEAN
1=True
Enables closing
BLK_OPEN
BOOLEAN
0=False
Blocks opening
BLK_CLOSE
BOOLEAN
0=False
Blocks closing
AU_OPEN
BOOLEAN
0=False
Executes the command for open direction
1)2)
AU_CLOSE
BOOLEAN
0=False
Executes the command for close direction
1)2)
ITL_BYPASS
BOOLEAN
0=False
Discards ENA_OPEN and ENA_CLOSE interlocking
when TRUE
1) Not available for monitoring
2) Always direct operation
Table 865:
29GS Input signals
Name
Type
Default
Description
POSOPEN
BOOLEAN
0=False
Apparatus open position
POSCLOSE
BOOLEAN
0=False
Apparatus close position
ENA_OPEN
BOOLEAN
1=True
Enables opening
ENA_CLOSE
BOOLEAN
1=True
Enables closing
BLK_OPEN
BOOLEAN
0=False
Blocks opening
BLK_CLOSE
BOOLEAN
0=False
Blocks closing
Table continues on next page
Section 9
1MAC059074-MB A
Control functions
966
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......